The Y43H steam pressure-reducing valve uses downstream-pressure feedback to lower inlet pressure to a set outlet value. Its pilot-operated piston design combines a pilot valve and main valve for steam lines where inlet pressure or demand varies. Select by inlet pressure, outlet setting, minimum differential and size.
| Pilot-operated piston | The pilot controls piston movement, changing the main-valve flow area. |
| Outlet-pressure feedback | A diaphragm senses downstream pressure while an adjusting spring sets the target. |
| Functional assemblies | The main valve contains the seat, disc and piston; the pilot contains a diaphragm, disc and springs. |
| Illustrated model | Y43H steam pressure-reducing valve |
| Nominal sizes | 1.6–4.0 MPa tables list DN15–DN500; 6.4–16 MPa tables list DN15–DN100 |
| Nominal pressure and test | PN1.6, 2.5, 4.0, 6.4, 10 and 16 MPa; shell test is 1.5 × PN |
| Outlet pressure at 1.6/2.5/4.0 MPa | 0.04–1.0, 0.05–1.6 and 0.08–2.5 MPa, respectively |
| Outlet pressure at 6.4/10/16 MPa | 0.2–3.5, 0.5–3.5 and 0.5–4.5 MPa, respectively |
| Minimum differential | 0.07, 0.1, 0.15, 0.4, 0.5 and 0.8 MPa for the listed ratings |
| Main materials | WCB body; 2Cr13 seats, discs and guides; 1Cr18Ni9Ti diaphragm |
| Performance references | Pressure and flow deviations to GB 12246; leakage to GB 12245 |
Inquire Now